“Without prejudice to the above denials, it is submitted that the technical experts should confer about the prospects of the cleaning succeeding as this may be an ineffective and unnecessary process.”
“Firstly, it will be apparent from what I have said above in relation to the brickwork that I am satisfied that there is ample evidence that the cavity trays were set back to a significantly greater extent than the 5mm specified, that is by at least 20mm (as agreed in the Joint Statement) and by up to 65mm as observed by Ms Hoey. The setting back of the cavity trays even further than specified must have exacerbated the effect of permitting more moisture to penetrate the brickwork and, since I accept Ms Hoey’s opinion that that is the probable cause of the damp appearance of the brickwork, that must have been contributed to by Marbank’s breach of the specification. Other than the suggestion of Mr Satow that the mortar joints could be described as bucket-handled, that is slightly concave, there does not seem to be any dispute that the joints were also flush, rather than recessed which, even if the cavity trays had not been so far set back, would have prevented the exposure of the edge of the cavity tray.”